Model Predictive Control

In mpc calibration mode, each TRV is driven by a per-room Model Predictive Controller that learns the room's thermal behaviour and computes a valve opening % directly. Every numerical piece is a pure, separately unit-tested function fed synthetic thermal simulations, so the controller is testable without hardware.

Dependency: scipy, declared in manifest.json requirements. A heavier wheel but justified; this is the single biggest quality lever. numpy is already present in HA core. (do-mpc/cvxpy were considered and rejected for v1 as too heavy.) scipy is synchronous, so the coordinator runs the MPC observe/identify/optimise math in an executor job (hass.async_add_executor_job), keeping the event loop unblocked; each TRV has its own controller, so concurrent jobs never share state.

One cycle of the learning loop, end to end:

flowchart LR
    M["measurement<br>(raw area temperature)"] --> O["observe()"]
    O --> H["history<br>raw transitions, capped,<br>gaps > 30 min skipped"]
    H --> I["identify_parameters<br>bounded least_squares,<br>prior-regularised"]
    I --> P["ThermalParams<br>(gain, loss)"]
    O --> K["Kalman filter<br>predict over previous valve/outdoor,<br>then update with the measurement"]
    P --> K
    K --> ET["estimated_temperature"]
    ET --> V["optimize_valve<br>receding horizon,<br>bounded scalar minimise"]
    P --> V
    F["hourly forecast<br>(preconditioning)"] -.-> V
    V --> W["valve %<br>clamped to 0–100"]
Hold "Alt" / "Option" to enable pan & zoom

Thermal model

Room dynamics are modelled as linear first-order (single RC node):

dT/dt = gain·u − loss·(T − outdoor)

with u ∈ [0, 1] the valve fraction. Discretised (control/mpc/model.py: predict_step):

T[n+1] = T[n] + dt · (gain·valve − loss·(T[n] − outdoor))

The model has no solar or supply-temperature term: gain is a single learned constant (see the constant-supply-temperature assumption below).

  • gain — K per minute at full valve (how fast a fully-open valve heats the room).
  • loss — 1/minute coupling to the outdoor delta (how fast the room leaks heat).

Assumption: constant supply temperature

gain is a single learned constant, so the model assumes a fixed heat output at a given valve opening. That holds for a radiator fed at a steady water temperature (a fixed-flow boiler, electric). It does not hold for a weather-compensated hydronic system — district heating, or a condensing boiler on an outdoor-reset curve — where the supply temperature rises as it gets colder, so the same opening emits more heat in harsh weather.

The model captures the loss side of harsh weather (loss·(room − outdoor) grows with the gradient) but not the output side. Because the fit runs over a rolling window it tracks a slowly-drifting supply temperature, and because control is closed-loop the room still reaches target — but the model is mis-specified: the fitter partly absorbs the weather-dependent emission into a distorted loss, the residual error (model_error) runs higher, preconditioning is less reliable, and a fast supply-temperature swing causes transient over/undershoot until the fit catches up. The poor-fit repair surfaces a TRV whose model can't fit, and on such systems offset mode (which defers modulation to the valve's own loop) is usually the better choice. The proper fix — modelling emission as k·valve·(supply − room) given a supply-temperature sensor — is recorded as future work in ADR-0004.

System identification

System identification replaces ad-hoc EMA inference with scipy.optimize.least_squares fitting (gain, loss) over a rolling window of (t, T, u, T_out) transition samples, with bounds and L2 regularisation toward priors (identify_parameters in control/mpc/model.py). It produces parameter estimates plus residual diagnostics.

  • Prior regularisation. The residual vector appends _PRIOR_WEIGHT · (gain − prior.gain) and _PRIOR_WEIGHT · (loss − prior.loss) to the prediction residuals, so a cold start (or degenerate data) stays near the safe priors (DEFAULT_GAIN, DEFAULT_LOSS). With fewer than MIN_SAMPLES (6) transitions, the prior is returned unchanged.
  • Physical bounds. The fit runs inside bounds=([0, 0], [MAX_GAIN, MAX_LOSS])MAX_GAIN = 2.0 K/min at full valve, MAX_LOSS = 1.0 /min. A radiator gaining 2 K/min or a room with a 1-minute thermal time constant is already absurd; anything the solver pushes past these is degenerate data, not physics. Finite bounds also keep the optimiser's rollout from overflowing on runaway parameters. The starting point x0 is clamped inside the bounds, whatever a restored prior claims.
  • Success/finite rejection. If result.success is false, or either fitted value is non-finite, the prior (the last good parameters) is kept — degenerate data (all-identical samples, NaN creep) can make the solver give up or return garbage.

The fit's quality is surfaced per TRV: MpcController.fit_rmse() returns the root-mean-square residual (K/step) of the current (gain, loss) over the sample history, exposed as the model_error attribute on the <trv>_mpc_learning_status diagnostic sensor (alongside heating_gain, heat_loss, and samples) as a model-confidence figure.

Kalman observer

A small in-house scalar Kalman filter (control/mpc/observer.py) is wired into MpcController.observe(): each observation projects the previous estimate across the just-elapsed transition (the previous valve/outdoor held for dt) and corrects with the new measurement.

  • predict(state, valve, outdoor, params, dt) advances the estimate through predict_step and propagates the variance through the model Jacobian (jac = 1 − dt·loss), adding PROCESS_VAR.
  • update(state, measurement) applies the standard Kalman gain variance / (variance + MEASUREMENT_VAR).
  • Q/R are fixed (PROCESS_VAR = 0.01, MEASUREMENT_VAR = 0.04) but tunable later; the state persists with the controller and old stores without it load cleanly.
  • Variance ceiling. The predicted variance is capped at MAX_VARIANCE (25.0): a 5 K standard deviation already means "the estimate is worthless, trust the next measurement almost entirely" (Kalman gain ~0.998). Without a ceiling, a long prediction gap or corrupt restored state could grow the variance without bound and destabilise subsequent updates.

The optimiser plans from the filtered estimated_temperature.

Raw transitions for identification

System identification deliberately consumes raw transitions — fitting the model to its own Kalman-smoothed output would be circular. The filter only shapes what the optimiser plans from.

Gap re-anchoring

Transitions longer than MAX_SAMPLE_DT_MIN (30 min — an HA freeze, restart gap, or long device outage) carry essentially no information about the valve's effect: the room has re-equilibrated several times over, and a huge dt skews the fit and blows up the Kalman projection. Such gaps re-anchor the estimate on the new measurement (KalmanState(temp=measurement, variance=MEASUREMENT_VAR)) instead of being learned from. Non-finite observations are ignored outright.

Receding-horizon optimizer

The hand-rolled coarse/fine grid search is replaced by a scipy bounded minimiser (control/mpc/optimizer.py: optimize_valve) minimising a quadratic tracking cost over a receding horizon (default 6 steps — about 6 minutes at the 1-minute control cycle, DEFAULT_HORIZON) with an optional control-effort penalty. Bounds 0 ≤ u ≤ max_opening. A single held move is optimised per cycle, which suits a TRV that keeps its opening until the next update.

optimize_valve/compute_valve_pct accept outdoor as either a scalar or a sequence (a shorter series holds its last value past its end). The computed valve opening is always clamped to [0, 100] % as a final hardware clamp, whatever the caller passed as max.

When the device is not heating (idle/off/window/gated), the valve is explicitly driven to 0% rather than left at its last commanded opening — see Device control.

Multi-TRV distribution: one room/zone-level command is distributed to individual TRVs with per-valve deficit compensation.

Forecast preconditioning

Opt-in (forecast_preconditioning switch, MPC mode only). Normally the optimiser plans against the current outdoor temperature held flat. With this on, the coordinator fetches the configured weather entity's hourly forecast (via weather.get_forecasts, cached and refreshed at most every PRECONDITION_FORECAST_REFRESH_SECONDS), interpolates it onto the control step over preconditioning_horizon hours (control/forecast.py: expand_forecast, capped at PRECONDITION_MAX_STEPS), and feeds that per-step outdoor series into optimize_valve over the extended horizon — so a radiator pre-heats ahead of a forecast cold spell.

To stay comfort-safe it can only raise the valve — the max-of-two optimisations rule (the pure preconditioned_valve_pct in control/mpc/controller.py):

commanded = max(react-to-now valve, forecast valve)

The plain optimisation answers "how open right now"; the second optimisation over the look-ahead series may ask for more heat ahead of a cold spell. Taking the max guarantees preconditioning can only pre-heat — the present is never under-heated just because the future looks warm.

The forecast fetch is best-effort (failures no-op); a missing weather entity raises a repair.

Persistence

Learned parameters, the sample history, and the observer state are saved via a coordinator Store and restored on startup with safe cold-start priors. See Persistence for the store schema and migration semantics.

Numerical hardening summary

  • The fit runs inside physical bounds (MAX_GAIN/MAX_LOSS) and keeps the prior on solver failure or non-finite output.
  • The Kalman variance is ceilinged (MAX_VARIANCE).
  • Non-finite observations are ignored; gaps longer than MAX_SAMPLE_DT_MIN re-anchor the estimate instead of being learned from.
  • Restored state is validated: non-finite params rejected, parameters re-clamped to the fit bounds, bad samples dropped, variance capped (Python's json round-trips NaN/Infinity, so a corrupted store can hand back "numbers" that would poison every prediction).
  • The computed valve % is always clamped to [0, 100].

Next: Device control — how MPC output and the other calibration modes become device commands.